Filling pressure of extinguishing agent bottle (MPa) |
4.2 |
5.6 |
|
Maximum system operating pressure (MPa) |
5.3(welding bottle) |
6.7(seamless cylinder) |
8.0 |
Charge density of extinguishing agent (kg/m3) |
≤950 |
≤1120 |
≤1080 |
Specification of extinguishing agent storage bottle |
70L、90L、120L、150L |
40L、70L、90L |
70L、90L |
20 ℃ to start the gas storage bottle filling pressure |
6.0 |
||
Start the gas storage bottle of 50 ℃ maximum working pressure (MPa) |
6.6 |
||
Minimum ambient temperature in the reserve |
-10℃ |
||
Ambient temperature in the bottle room |
0℃~+50℃ |
||
The fire extinguishing system starts the working |
DC24V±3V |
Sevofluropropane gas extinguishing system
-
1 overview
Hfc-227ea is a
colorless, odorless, non-conductive extinguishing agent with zero ozone layer
depletion potential (ODP).Sevoflurane fire extinguishing system is equipped
with automatic, electrical manual and mechanical emergency manual control mode,
according to different requirements, can be composed of unit independent
system, combined distribution system, the implementation of single zone and
multi-zone fire protection.Standard: GB25972
gas extinguishing system and components.2 application scope
It is mainly used
for the fire protection of key units such as computer room, telecommunication
center, underground engineering, offshore oil platform, library, archives,
treasure house and power distribution room.3 of
The system is
mainly composed of automatic alarm fire control system, extinguishing agent
storage bottle, starting gas storage bottle, bottle head valve, safety valve,
electromagnetic bottle head valve, selection valve, one-way valve, pressure
switch, frame, nozzle, pipeline system and other main components.