Model |
GQQ40/2.5 |
GQQ70/2.5 |
GQQ90/2.5 |
GQQ120/2.5 |
Volume of |
40 |
70 |
90 |
120 |
Maximum filling |
1150 |
|||
Maximum charge of |
46 |
80 |
103 |
138 |
Weight kg |
172 |
228 |
258 |
355 |
Single maximum |
72 |
127 |
163 |
217 |
Extinguishing agent |
≤10 |
|||
Drive gas filling |
2.5 |
|||
The environment |
0℃~50℃ |
|||
Ambient relative |
≤95%(40±2℃) |
|||
Single bottle set box size (length width height) |
470×370×1460 |
470×370×1920 |
700×610×1900 |
|
Start the way |
Electric start |
|||
Delay time s |
20~40 |
|||
The main power supply |
AC220V(50Hz) |
|||
Standby power |
DC24V |
Cabinet type fm-200 gas extinguishing equipment
-
The fire extinguishing device
of sevoflurane gas in cabinet is a kind of equipment which can automatically
detect and put out the fire by integrating the components of the storage
container of extinguishing agent, pipes, nozzles, fire detecting components and
controllers.Cabinet fire extinguishing device is a kind of
modern fire fighting equipment without installation of pipe network, compact
structure, portable, automatic monitoring, automatic alarm and automatic fire
extinguishing.It has the advantages of high extinguishing
efficiency, fast extinguishing speed, low toxicity of extinguishing agent, no
dirt on the equipment, good sealing performance of the extinguishing device,
and automatic and manual electrical control.Fire
extinguishing devices can be set up separately to protect the protection areas
with smaller space, or several sets can be set up together to protect the
protection areas with larger space.Because there is no need to
install pipe network, the whole device is set in the protected area. In case of
fire, it can automatically spray extinguishing agent directly into the
protected area, which is quick and convenient.Execution
standard: GB16670 “cabinet type gas extinguishing device”.2 application
scopeThe
products are mainly applied to the fire protection of key places such as
computer room, communication base station, library, archives, valuables
warehouse, power station, telecommunication center, power distribution room and
clean workshop.3 of
The fire
extinguishing device is mainly composed of box body, bottle head valve,
extinguishing agent storage bottle, pressure switch (pressure signal device),
nozzle, fire alarm and fire extinguishing controller, fire detector, manual
control box, sound-light alarm box, vent gas display lamp and other parts, and
the control part can be connected with the computer control center.
نقد و بررسیها
هنوز بررسیای ثبت نشده است.
نقد و بررسیها
هنوز بررسیای ثبت نشده است.